XB4BS9445EX

REDEMERGSTOPTRIGGEREN13850KEYR

Trade Price

POA

Per

1

Unit

Pack Quantity

XB4BS9445EX

Information

This product is part of the Harmony XB4 - ATEX D range, an offer of Ø 22mm metal pushbuttons, switches and pilot lights for explosive atmosphere. This emergency switching off pusbutton comes with a mushroom head and key number 455. This offer is specially designed for explosive atmosphere. It is designed for used in dust zone 21-22. It comes with trigger action and mechanical latching and key release operation. It has 1 NO and 1 NC contact with slow-break operation. This is a metal emergency stop pushbutton with a 40mm diameter mushroom head. This offer is specially designed for applications in Oil and Gas industry as well as Food and beverage, car gas stations etc. It is an IP66, IP69, IP69K and IP67 rated product and comes with INERIS 04ATEX9004U certification. It is easily installed into a standard 22mm diameter panel cut-outs and connected to control circuits with screw-clamp connections. The Harmony XB4 range offers innovative features for simple and efficient use. The Harmony XB4 - ATEX is the most comprehensive explosive Atmospheres range covering most applications.

Technical Specifications

Range of product

Harmony XB4

Product or component type

Complete emergency stop push-button

Device short name

XB4

bezel material

Chromium plated metal

Fixing collar material

Zamak

Head type

Standard

Mounting diameter

22 mm

Sale per indivisible quantity

1

Dust zone

Zone 21 - 22

Type of operator

trigger action and mechanical latching

Reset

Key release

Operator profile

Red mushroom Ø 40 mm

Key number

455

Contacts type and composition

1 NO + 1 NC

Device mounting

Fixing hole - diameter: 22.5 mm 22.3 +0.4/0

Fixing center

>= 30 x 40 mm (support panel)

Fixing mode

Screw-fixed: 0.8…1.2 N.m

Embedding depth

43 mm

Marking

Ex tb IIIC

Shape of signaling unit head

Round

Key withdrawal position

Center

contact operation

Slow-break

contacts usage

Standard

Positive opening

With conforming to IEC 60947-5-1 appendix K

Operating travel

1.5 mm (NC changing electrical state) 4.3 mm (total travel)

Mechanical durability

300000 cycles

Connections - terminals

Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1

Tightening torque

0.8…1.2 N.m conforming to IEC 60947-1

Shape of screw head

Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver

Contacts material

Silver alloy (Ag/Ni)

Short-circuit protection

10 A cartridge fuse type gG conforming to IEC 60947-5-1

[Ith] conventional free air thermal current

10 A conforming to IEC 60947-5-1

[Ui] rated insulation voltage

600 V (pollution degree 3) conforming to IEC 60947-1

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-1

[Ie] rated operational current

3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1

Electrical durability

1000000 cycles AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C 1000000 cycles DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C

Electrical reliability

Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to IEC 60947-5-4 Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to IEC 60947-5-4

Protective treatment

TH

Ambient air temperature for operation

-40…70 °C

Overvoltage category

I conforming to IEC 60536

IP degree of protection

IP66 conforming to IEC 60529 IP69 IP69K IP67

IK degree of protection

IK03

Standards

IEC 60947-5-5 IEC 60079-0:2009 EN 60079-31:2009 IEC 61000-6-2 ISO 13850 IEC 60079-0:2007 IEC 60079-31:2008

Directives

94/9/EC - ATEX directive

product certifications

INERIS 04ATEX9004U

Vibration resistance

5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6

Shock resistance

30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

4.0 cm

Package 1 Width

15.0 cm

Package 1 Length

12.0 cm

Package 1 Weight

168.0 g

Unit Type of Package 2

S01

Number of Units in Package 2

10

Package 2 Height

15.0 cm

Package 2 Width

15.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

1.87 kg

Warranty

18 months

Document Links

Datasheet