NDN103A

MCB 1P 10kA/15kA D-3A 1M

Trade Price

£26.51

Per

1

Unit

EA

Pack Quantity

12

NDN103A

Technical Specifications

Neutral position

without neutral

Number of protected poles

1

Number of poles

1 P

Type of pole

1 P

Concurrently switching N-neutral

No

Number of modules

1

Top connection alignement for modular devices

Aligned terminal

Bottom connection alignement for modular devices

Aligned terminal

Rated short circuit breaking capacity Icn AC according IEC60898-1

10 kA

Rated operational voltage Ue

240 / 415 V

Type of supply voltage

AC

Rated insulation voltage

500 V

Max operating voltage

440 V

Rated impulse withstand voltage

6000 V

Minimum threshold voltage (Ue min)

12 V

Rated current

3 A

Rated service breaking capacity Ics AC according IEC 60898-1

7.5 kA

min/maxi threshold value of the AC thermal operation

1.13 / 1.45 In

Magnetic regulating currrent

10 / 14.4 In

min/maxi threshold value of the DC magnetic operation

15 / 30 In

min/maxi threshold value of the DC thermal operation

1.13 / 1.45 In

Rating current -10°C according to IEC 60947

4 A

Rating current -15°C according to IEC 60947

4.07 A

Rating current -20°C according to IEC 60947

4.15 A

Rating current -25°C according to IEC 60947

4.22 A

Rating current -5°C according to IEC 60947

3.93 A

Rating current 0°C according to IEC 60947

3.85 A

Rating current 10°C according to IEC 60947

3.7 A

Rating current 150°C according to IEC 60947

3.62 A

Rating current 20°C according to IEC 60947

3.54 A

Rating current 25°C according to IEC 60947

3.45 A

Rating current 30°C according to IEC 60947

3.37 A

Rating current 35°C according to IEC 60947

3.28 A

Rating current 40°C according to IEC 60947

3.19 A

Rating current 45°C according to IEC 60947

3.1 A

Rating current 5°C according to IEC 60947

3.78 A

Rating current 50°C according to IEC 60947

3 A

Rating current 55°C according to IEC 60947

2.9 A

Rating current 60°C according to IEC 60947

2.8 A

Rating current 65°C according to IEC 60947

2.69 A

Rating current 70°C according to IEC 60947

2.58 A

Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1

10 kA

Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2

15 kA

Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2

15 kA

Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1

10 kA

Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2

15 kA

Rating current -25°C

3.76 A

Rating current -20°C

3.69 A

Rating current -15°C

3.63 A

Rating current -10°C

3.57 A

Rating current -5°C

3.5 A

Rating current 0°C

3.44 A

Rating current 5°C

3.38 A

Rating current 10°C

3.32 A

Rating current 25°C

3.15 A

Rating current 30°C

3 A

Rating current 35°C

2.97 A

Rating current 40°C

2.93 A

Rating current 45°C

2.91 A

Rating current 50°C

2.87 A

Rating current 55°C

2.86 A

Rating current 60°C

2.85 A

Rating current 65°C

2.84 A

Rating current 70°C

2.83 A

Correction factor of rating current for 2 devices placed side-by-side

1

Correction factor of rating current for 3 devices placed side-by-side

0.95

Correction factor of rating current for 4 and 5 devices placed side-by-side

0.9

Correction factor of rating current for 6 devices placed side-by-side

0.85

Correction factor of magnetic tripping with 100 Hz

1.1

Correction factor of magnetic tripping with 200 Hz

1.2

Correction factor of magnetic tripping with 400 Hz

1.5

Correction factor of magnetic tripping with 60 Hz

1.1

Depth of installed product

70 mm

Height of installed product

83 mm

Width of installed product

17.5 mm

Frequency

50 to 60 Hz

Maximum power loss per pole according to the product standard

3 W

Total power loss under IN

2.24 W

Power loss per pole at In

2.24 W

Electric endurance in number of cycles

4000

Number of mechanical operations

20000

Type of top connection for modular devices

with screw

Tightening torque

2,8Nm